Fujitsu Error Code E2:00: Room Temp Sensor Open Circuit

Severity
Warning
Type
digital display
Estimated repair cost: $100 — $250 (parts + labor)
Warning: The indoor unit isn't reading the room temperature, so the system has shut down to prevent overheating or freezing. This requires professional diagnosis.

How to Fix Fujitsu Code E2:00

  1. Step 1: Power cycle the unit by turning off the breaker that supplies power to the indoor unit for 5 minutes, then turn it back on. This may reset the system and clear a temporary error.
  2. Step 2: Visually inspect the area around the indoor unit for any obvious signs of damage, such as chewed wires or loose connections. Do not open the unit.
  3. Step 3: If the error persists after power cycling and you see no obvious damage, contact a qualified HVAC technician to diagnose and repair the issue.

How to Reset Fujitsu Code E2:00

  1. Turn off the unit using the remote control or wall controller.
  2. Turn off the circuit breaker for the outdoor and indoor units. Wait 60 seconds.
  3. Restore power at the breaker.
  4. Turn the unit on with the remote control. If the error returns, the fault needs professional diagnosis.

Resetting clears the code from the display but does not fix the underlying fault. If the code returns after reset, proceed to the diagnostic steps above.

What Does Fujitsu Error Code E2:00 Mean?

The Fujitsu error code E2:00 indicates that the indoor unit's main control board isn't receiving a signal from the room temperature sensor. This sensor, also called a thermistor, is responsible for telling the system the current room temperature. Without this information, the unit can't properly regulate heating or cooling, and the system will lock out to prevent potential issues like the unit running constantly or not at all. This error is specific to the indoor unit and will prevent it from operating until the issue is resolved. It's important to address this promptly to restore comfortable temperatures and efficient operation.

Common Causes

  • Faulty room temperature sensor (thermistor)
  • Loose or damaged wiring between the sensor and the main control board
  • Corrosion on the sensor or control board connections
  • Defective main control board in the indoor unit
  • Rodent damage to the sensor wiring

Diagnostic Steps

If... Check Expected
Unit displays E2:00 error Measure resistance across the room temperature sensor terminals at the main control board Resistance should match the thermistor's temperature/resistance chart (typically around 10k ohms at 25°C).
Resistance is outside the expected range Disconnect the sensor and measure resistance directly at the sensor terminals Same resistance as measured at the board. If different, wiring is the issue.
Sensor resistance is correct Check voltage at the sensor input on the main control board Typically 5V DC
Voltage is absent or unstable Inspect the main control board for signs of damage (burn marks, corrosion) Board should appear clean and undamaged.

Applicable Fujitsu Models

Replacement Parts

Part OEM Number Est. Cost Where to Buy
Room Temperature Sensor (Thermistor) 9704378071
Main Control Board

Related Codes on Same Models

Other codes that affect the same Fujitsu model families as E2:00.

Code Description Severity
E0:00 Communication Error (Indoor to Remote) Warning
E1:00 Communication Error (Indoor to Outdoor) Warning
E3:00 Room Temp Sensor Short Circuit Warning
E4:00 Indoor Coil Sensor Open Warning
E5:00 Indoor Coil Sensor Short Warning
E6:00 Outdoor Coil Sensor Fault Warning
E7:00 Outdoor Ambient Sensor Fault Warning
E8:00 Indoor Fan Motor Fault Warning
E9:00 Drain Pump / Float Switch Warning
EE:00 Communication Error (Multi-System) Warning