E517 🟡 Repair Required

Navien Error Code E517: Water Flow Switch Failure

⚠️ System is locked out; no heat or hot water until the issue is fixed, but this is not an immediate safety emergency.

How to Fix Navien Code E517

  1. Step 1: Check the system pressure gauge on the front of the unit. It should read between 12 and 25 psi. If below 12 psi, open the fill valve to repressurize to 15 psi. Do not exceed 25 psi.
  2. Step 2: Try pressing the 'Reset' button on the control panel for 3 seconds to clear the lockout. If the error returns immediately, proceed to step 3.
  3. Step 3: If the pressure is fine and reset doesn't work, call a qualified HVAC technician. Do not open the unit—there are live electrical connections and gas components inside.
Type: digital display Display: front panel

What Does Navien Error Code E517 Mean?

The E517 error on your Navien boiler or water heater means the water flow switch did not close within 10 seconds after a call for heat or hot water. The flow switch is a safety device that confirms water is actually moving through the heat exchanger before the burner fires. If the switch doesn't close, the unit locks out to prevent overheating or damage to the heat exchanger. This is commonly caused by a stuck or failed flow switch, but can also happen when the system is low on water pressure, has air trapped in the pipes, or the pump isn't running. Some Navien models use a magnetic reed switch; others use a Hall effect sensor. On combi units (NCB), the internal circulator must be running for flow to occur. On tankless water heaters (NPE, NPN), the flow switch is triggered by the pressure drop across an internal orifice when a hot water tap is opened. You'll need to check the system pressure, bleed air from the unit and zone piping, and verify the pump is getting power. If those are all fine, the flow switch itself is likely defective and needs replacement.

Common Causes of Navien Code E517

  • Defective or stuck flow switch (reed switch stuck open, or paddle stuck from debris)
  • Low system water pressure below 12 psi (boiler) or blocked supply filter (tankless)
  • Air trapped in heat exchanger or pump head preventing water flow
  • Failed internal or external system circulator pump (no movement/flow)
  • Wiring issue or loose connection at flow switch harness

Applicable Navien Models

Source Documentation

This error code is documented in 6 official Navien technical manuals.

📄
NFB-H Installation & Operation ManualPage 116
ReasonAbnormal DIP Switch
ActionCheck DIP switch settings.
📄
Navien NCB-H Installation & Operation ManualPage 130
ReasonAbnormal DIP Switch
ActionContact technical support at 1-800-519-8794.
📄
Navien NFB-H Installation & Operation ManualPage 116
ReasonAbnormal DIP Switch
ActionCheck DIP switch settings.
📄
Navien NFC-H Installation & Operation ManualPage 127
ReasonAbnormal operation: Dip switch setting
ActionManual RESET
📄
Navien NHB-H Installation & Operation ManualPage 119
ReasonAbnormal DIP Switch
ActionCheck DIP switch settings.
📄
Navien NPF Installation & Operation ManualPage 127
ReasonAbnormal DIP switch settings
ActionThis error occurs when the furnace’s capacity does not match with the main controller. ● If this error occurs continuously, contact Technical Support at 1-800-519-8794
🔧

Need a Pro to Fix Navien Code E517?

A licensed HVAC technician can diagnose and fix this issue quickly.

Find a Licensed Tech Near You →

Replacement Parts for Navien Tankless Water Heater Code E517

Flow Switch Assembly (Reed Switch) OEM: NAV-30031974B
Water Flow Sensor (Hall Effect) OEM: NAV-30025068A
Internal Circulator Pump