Navien Error Code E822: Overcooling of the air conditioning coil (Evaporator coil).

Severity
Warning
Type
digital display
Estimated repair cost: $100 — $250 (parts + labor)
Warning: Your Navien air conditioner has detected that the evaporator coil is too cold, which can cause icing and system shutdown. This requires diagnosis and repair.

How to Fix Navien Code E822

  1. Step 1: Check and replace your air filter. A dirty air filter is the most common cause of restricted airflow.
  2. Step 2: Ensure that all supply and return air vents are open and not blocked by furniture or other obstructions.
  3. Step 3: After completing steps 1 and 2, reset the unit by turning it off and then back on at the breaker. If the error reappears, call a qualified HVAC technician.

How to Reset Navien Code E822

  1. Turn off the unit using the power button on the front panel.
  2. Turn off the gas supply valve.
  3. Turn off the circuit breaker supplying power to the unit. Wait 30 seconds.
  4. Restore power at the breaker, then open the gas valve.
  5. Turn the unit back on. If the error returns, the underlying issue needs repair.

Resetting clears the code from the display but does not fix the underlying fault. If the code returns after reset, proceed to the diagnostic steps above.

What Does Navien Error Code E822 Mean?

The E822 error code on your Navien indicates that the evaporator coil in your air conditioning system is experiencing overcooling. This typically happens when the coil gets too cold, often leading to ice formation. This icing restricts airflow, reduces cooling efficiency, and can potentially damage the compressor if left unaddressed. The Navien system is designed to shut down to prevent further damage when this condition is detected. Think of it like your car overheating – the system is protecting itself.

Common Causes

  • Refrigerant leak causing low refrigerant charge
  • Restricted airflow across the evaporator coil due to a dirty air filter or blocked ductwork
  • Faulty evaporator thermistor reading incorrect temperatures
  • Failed or malfunctioning TXV (thermal expansion valve) causing overfeeding of refrigerant

Diagnostic Steps

If... Check Expected
Evaporator coil is iced over Measure refrigerant pressures (suction and liquid line) Low suction pressure, potentially normal to low liquid pressure
Refrigerant pressures are abnormal Check superheat and subcooling High superheat, low subcooling indicates low charge or TXV issue
Airflow seems restricted Measure static pressure across the evaporator coil High static pressure indicates airflow restriction
Suspect thermistor issue Measure resistance of the evaporator thermistor at a known temperature Compare resistance to the thermistor's temperature/resistance chart. Deviation indicates a faulty thermistor.

Applicable Navien Models

Source Documentation

Referenced in 1 official Navien technical manual.

ManualPageReasonAction
Navien NPF Installation & Operation Manual129Overcooling of the air conditioning coil (Evaporator coil).This error occurs when the supply air (SA) temperature is abnormal. ● Check the status of the air conditioning coil (Evaporator coil). ● Check if the duct’s filter is clean. ● Check if the set cooling airflow is suitable for the cooling capacity.

Replacement Parts

Part OEM Number Est. Cost Where to Buy
Evaporator Thermistor
TXV (Thermal Expansion Valve)
Air Filter

Related Codes on Same Models

Other codes that affect the same Navien model families as E822.

Code Description Severity
E001 Ignition Failure Warning
E003 Abnormal Ignition Warning
E004 False Flame Detection Warning
E012 Flame Loss Warning
E016 Overheating Warning
E030 Exhaust Overheat Sensor Warning
E031 Inlet Thermistor Open/Short Warning
E046 Outlet Thermistor Open/Short Warning
E047 DHW Thermistor Open/Short Warning
E060 Fan Motor Abnormality Warning